19 inches 1U standard rack installation;
1 input and 9 outputs;
Good insulation for output terminals
Large discharge current and low residual voltage
Remote signal alarm connectors (dry contacts of remote signal alarm is closed at normal operation while open at fault condition).
Product model | DCPD6 |
Nominal operating voltage Uo | -48V |
Max. continuous operating voltage Uc | -75V |
Frequency | 0Hz |
Protection modes | -48V—RTN,-48V—PE,RTN—PE |
Nominal discharge current In (8/20 us waveform) | -48V—RTN:10kA;-48V—PE:15kA;RTN—PE:15kA |
Max. discharge current Imax (8/20 us waveform) | -48V—RTN;15kA;-48V—PE:15kA;RTN—PE;15kA |
Surge durability(8/20 us waveform) | -48V—RTN:10kA;-48V—PE:15kA;RTN—PE:15kA |
Rated load current IR | Input:100A(9 outputs, rated current 11A or Max. current 20A for each output) |
Limiting voltage | -48V—RTN≤500V |
Connection | Serial connection |
Distribution capacity | One input and 9 outputs |
Rated current of breaker | 20A(for each output) |
Local alarm indicator | None |
Remote signal alarm connectors | Dry contacts 1 and 3 are closed at normal operation while open at fault. |
Connector | Input: double crimping connectors |
Output: Spring crimping connectors | |
Wire area | Input: 16~25mm 2 |
Output: 2.5~10mm2 | |
Remote signal alarm:0.2~2mm2 | |
Grounding connection | 2 grounding terminals of Φ11mm on the front panel, M6 bolt for fixation |
dimensions | 482.6mm×228mm×43.6mm |